EasyManua.ls Logo

Emerson Vilter MicroVission - Multi-IO Board Analog I;O; Table 2-2. Multi-IO Board (Analog I;O)

Emerson Vilter MicroVission
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 – 4
Section 2 Hardware Architecture
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Compressor Motor Starter Auxiliary Input:
This input looks for a feedback signal from the com-
pressor starter, conrming that the compressor
starter is energized.
Multi-IO Board Analog I/O
For information about each Analog I/O signal, see Table
2-2. Multi-IO Board (Analog I/O).
Process Temperature
Default signal is RTD. Process temperature calibra-
tion is set in the calibration screen.
Oil Temperature
Default signal is RTD. Oil temperature calibration is
set in the calibration screen.
Discharge Temperature
Default signal is RTD. Discharge temperature calibra-
tion is set in the calibration screen.
Suction Temperature
Default signal is RTD. Suction temperature calibra-
tion is set in the calibration screen.
Filter Out Pressure
Default signal is 4-20mA. Filter Out pressure trans-
ducer range and calibration are set in the calibration
screen.
Filter In Pressure
Default signal is 4-20mA. Filter In pressure transducer
Table 2-2. Multi-IO Board (Analog I/O)
Connector on
Mul-IO Board
I/O # Descripon Channel Type Signals Type
X6 – 2 1 Process Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X6 – 5 2 Oil Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X7 – 2 3 Discharge Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X7 – 5 4 Sucon Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X8 – 2 5 Filter Out Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X8 – 5 6 Filter In Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X9 – 2 7 Oil Manifold Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X9 – 5 8 Discharge Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X10 – 2 9 Sucon Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X10 – 5 10 Motor Amps (4-20 mA) INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X12 – 1 11 Compressor VFD OUTPUT 4-20 mA
X12 – 3 12 Auxiliary Output #1 OUTPUT 4-20 mA
X12 – 5 13 Auxiliary Output #2 OUTPUT 4-20 mA
X13 – 1 14 Auxiliary Output #3 OUTPUT 4-20 mA
X13 – 3 15 Auxiliary Output #4 OUTPUT 4-20 mA
X13 – 5 16 Auxiliary Output #5 OUTPUT 4-20 mA
range and calibration are set in the calibration screen.
Oil Manifold Pressure
Default signal is 4-20mA. Oil manifold pressure trans-
ducer range and calibration are set in the calibration
screen.
Discharge Pressure
Default signal is 4-20 mA. Discharge pressure trans-
ducer range and calibration are set in the calibration
screen.
Suction Pressure
Default signal is 4-20 mA. Suction pressure trans-
ducer range and calibration is set in the calibration
screen.
Motor Amps
Default signal is a 4-20 mA. The Motor Amps calibra-
tion is set in the calibration screen.
Compressor VFD
Default signal is a 4-20 mA output to control com-
pressor motor speed with a Variable Frequency Drive
(VFD).
Auxiliary Output #1 - #5:
Optional outputs that can be congured in user de-
ned manner. When Condenser Control option is se-
lected in the conguration screen, Auxiliary Output
can be used to control Condenser VFD Fan.

Table of Contents

Other manuals for Emerson Vilter MicroVission

Related product manuals