13 – 3
Section 13 • Data Backup
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Factory Reset
The Factory reset button offers the operator the ability
to reset all the MicroVission setpoints back to the facto-
ry default settings or a specic database. If the operator
nds that a screen will not load when selected, it is likely
that the database associated with that screen has been
corrupted. Unfortunately, data corruption is always a
possibility in any system. So, this function was designed
to help the operator to regain control, see Figure 13-2.
Reset
• This button initiates the process to revert the
MicroVission back to the factory default settings.
Setpoints Report
The setpoints report screen offers the operator ability
to generate a setpoints report for all screens. The re-
ports are stored as .csv les and can be saved to a USB
drive from Save/Load screen by selecting the “Setpoints
Report” option in Data Items section during backup of
database. The .csv le can be imported in any spread
sheet application. During operation, the operator can
generate reports at any time. See Figure 13-3: Data
Backup Screen - Setpoints Report.
All/ Select:
• Selecting “All” will include all screens in the report
that is generated. When “Select” option is selected,
the operator can choose which screens will be includ-
ed in the report.
Generate:
• This button initiates the process to generate set-
points report les.
Figure 13-3. Data Backup Screen - Setpoints Report