EasyManuals Logo
Home>Endress+Hauser>Measuring Instruments>MODBUS RS485

Endress+Hauser MODBUS RS485 User Manual

Endress+Hauser MODBUS RS485
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Installation Proline Promag 53 MODBUS RS485
12 Endress+Hauser
Transporting flanged devices DN 300 (12")
Use only the metal eyes on the flanges for transporting the device, lifting it and positioning the
sensor in the piping.
"
Caution!
Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing. This
would buckle the casing and damage the internal magnetic coils.
a0004295
Fig. 5: Transporting sensors with DN > 300 (12")
3.1.3 Storage
Note the following points:
Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors ä 120.
The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
Choose a storage location where moisture does not collect in the measuring device. This will help
prevent fungus and bacteria infestation which can damage the lining.
Do not remove the protection plates or caps on the process connections until you are ready to
install the device. This is particularly important in the case of sensors with PTFE linings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser MODBUS RS485 and is the answer not in the manual?

Endress+Hauser MODBUS RS485 Specifications

General IconGeneral
BrandEndress+Hauser
ModelMODBUS RS485
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals