Technical data Proline Prowirl F 200 PROFIBUS PA
192 Endress+Hauser
Pulse/frequency/switch output
Pulse output
Failure mode No pulses
Frequency output
Failure mode Choose from:
Actual value
0 Hz
Defined value: 0 to 1 250 Hz
Switch output
Failure mode Choose from:
Current status
Open
Closed
PROFIBUS PA
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Error current FDE (Fault
Disconnection Electronic)
0 mA
Local display
Plain text display With information on cause and remedial measures
Backlight Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Operating tool
Via digital communication:
PROFIBUS PA
Via service interface
Plain text display With information on cause and remedial measures
Low flow cut off The switch points for low flow cut off are user-selectable.
Galvanic isolation All outputs are galvanically isolated from one another.
Protocol-specific data PROFIBUS PA
Manufacturer ID 0x11
Ident number 0x1564
Profile version 3.02
Device description files (GSD,
DTM, DD)
Information and files under:
www.endress.com
www.profibus.org