Proline Promag H 300 PROFINET Technical data
Endress+Hauser 193
Maximum switching
capacity (passive)
• DC 30 V, 0.1 A
• AC 30 V, 0.5 A
Assignable functions • Off
• On
• Diagnostic behavior
• Limit value:
• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Totalizer 1-3
• Temperature
• Electronic temperature
• Flow direction monitoring
• Status
• Empty pipe detection
• Low flow cut off
User-configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable
I/O) during device commissioning.
The following inputs and outputs are available for assignment:
• Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Pulse/frequency/switch output
• Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Status input
Signal on alarm Depending on the interface, failure information is displayed as follows:
PROFINET
Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure mode Choose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 20.5 mA