Commissioning Proline Promag H 300 PROFINET
90 Endress+Hauser
Apply I/O configuration
→  90
I/O alteration code
→  90
Parameter overview with brief description
Parameter Description User interface / Selection / 
User entry
Factory setting
I/O module 1 to n terminal numbers Shows the terminal numbers used by the I/O
module.
Not used
26-27 (I/O 1)
24-25 (I/O 2)
22-23 (I/O 3)
I/O module 1 to n information Shows information of the plugged I/O
module.
Not plugged
Invalid
Not configurable
Configurable
PROFINET
I/O module 1 to n type Shows the I/O module type. Off
Current output
*
Current input
*
Status input
*
Pulse/frequency/switch
output
*
Double pulse output
*
Relay output
*
Off
Apply I/O configuration Apply parameterization of the freely
configurable I/O module.
No
Yes
No
I/O alteration code Enter the code in order to change the I/O
configuration.
Positive integer 0
* Visibility depends on order options or device settings
10.5.6 Configuring the current input
The "Current input" wizard guides the user systematically through all the parameters that
have to be set for configuring the current input.
Navigation
"Setup" menu → Current input
Current input 1 to n
Terminal number
→  91
Signal mode
→  91
0/4 mA value
→  91
20 mA value
→  91
Current span
→  91