Operation options Proline Promag H 300 PROFINET
62 Endress+Hauser
Measuring device: Via CDI-RJ45 service interface
Device CDI-RJ45 service interface
Measuring device The measuring device has an RJ45 interface.
Web server Web server must be enabled; factory setting: ON
For information on enabling the Web server → 66
Measuring device: via WLAN interface
Device WLAN interface
Measuring device The measuring device has a WLAN antenna:
• Transmitter with integrated WLAN antenna
• Transmitter with external WLAN antenna
Web server Web server and WLAN must be enabled; factory setting: ON
For information on enabling the Web server → 66
8.4.3 Establishing a connection
Via service interface (CDI-RJ45)
Preparing the measuring device
1. Depending on the housing version:
Release the securing clamp or securing screw of the housing cover.
2. Depending on the housing version:
Unscrew or open the housing cover.
3. The location of the connection socket depends on the measuring device and the
communication protocol:
Connect the computer to the RJ45 connector via the standard Ethernet connecting
cable .
Configuring the Internet protocol of the computer
The IP address can be assigned to the measuring device in a variety of ways:
• Dynamic Configuration Protocol (DCP), factory setting:
The IP address is automatically assigned to the measuring device by the automation
system (e.g. Siemens S7).
• Hardware addressing:
The IP address is set via DIP switches → 43.
• Software addressing:
The IP address is entered via the IP address parameter (→ 88) .
• DIP switch for "Default IP address":
To establish the network connection via the service interface (CDI-RJ45): the fixed IP
address 192.168.1.212 is used → 45.
The measuring device works with the Dynamic Configuration Protocol (DCP), on leaving
the factory, i.e. the IP address of the measuring device is automatically assigned by the
automation system (e.g. Siemens S7).
To establish a network connection via the service interface (CDI-RJ45): set the "Default IP
address" DIP switch to ON. The measuring device then has the fixed IP address:
192.168.1.212. This address can now be used to establish the network connection.
1. Via DIP switch 2, activate the default IP address 192.168.1.212: → 45.
2. Switch on the measuring device.
3. Connect to the computer using a cable → 68.