Commissioning Proline Promag H 300 PROFINET
122 Endress+Hauser
Parameter overview with brief description
Parameter Description User interface / User entry Factory setting
Operating time Indicates how long the device has been in
operation.
Days (d), hours (h), minutes
(m) and seconds (s)
–
Reset access code Reset access code to factory settings.
For a reset code, contact your
Endress+Hauser service organization.
The reset code can only be entered via:
• Web browser
• DeviceCare, FieldCare (via service
interface CDI-RJ45)
• Fieldbus
Character string comprising
numbers, letters and special
characters
0x00
Using the parameter to reset the device
Navigation
"Setup" menu → Advanced setup → Administration
Parameter overview with brief description
Parameter Description Selection Factory setting
Device reset Reset the device configuration - either
entirely or in part - to a defined state.
• Cancel
• To delivery settings
• Restart device
• Restore S-DAT backup
*
Cancel
* Visibility depends on order options or device settings
10.7 Simulation
The Simulation submenu enables you to simulate, without a real flow situation, various
process variables in the process and the device alarm mode and to verify downstream
signal chains (switching valves or closed-control loops).
Navigation
"Diagnostics" menu → Simulation
‣
Simulation
Assign simulation process variable
→ 123
Process variable value
→ 123
Status input simulation 1 to n
→ 123
Input signal level 1 to n
→ 123
Current input 1 to n simulation
→ 123
Value current input 1 to n
→ 124