Commissioning Proline Promag H 300 PROFINET
92 Endress+Hauser
Terminal number
→ 92
Response time status input
→ 92
Terminal number
→ 92
Parameter overview with brief description
Parameter Description User interface / Selection /
User entry
Factory setting
Terminal number Shows the terminal numbers used by the
status input module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Assign status input Select function for the status input. • Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
Off
Active level Define input signal level at which the
assigned function is triggered.
• High
• Low
High
Response time status input Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
5 to 200 ms 50 ms
10.5.8 Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number
→ 93
Signal mode
→ 93
Assign current output 1 to n
→ 93
Current span
→ 93
0/4 mA value
→ 93
20 mA value
→ 94
Fixed current
→ 94
Damping output 1 to n
→ 94