Proline Promag H 300 PROFINET Commissioning
Endress+Hauser 93
Failure mode
→ 94
Failure current
→ 94
Parameter overview with brief description
Parameter Prerequisite Description User interface /
Selection / User
entry
Factory setting
Terminal number – Shows the terminal numbers
used by the current output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Signal mode – Select the signal mode for the
current output.
• Active
*
• Passive
*
Active
Assign current output 1 to n – Select process variable for
current output.
• Off
*
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
*
• Corrected
conductivity
*
• Temperature
*
• Electronic
temperature
• Reference
electrode potential
against PE
*
• Coil current shot
time
*
• Noise
*
• Coating measured
value
*
• Test point 1
• Test point 2
• Test point 3
Volume flow
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed current
Country-specific:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
0/4 mA value In the Current span parameter
(→ 93), one of the
following options is selected:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter 4 mA value. Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)