Proline Promag H 300 PROFINET Commissioning
Endress+Hauser 93
Failure mode
→  94
Failure current
→  94
Parameter overview with brief description
Parameter Prerequisite Description User interface / 
Selection / User
entry
Factory setting
Terminal number Shows the terminal numbers
used by the current output
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
Signal mode Select the signal mode for the
current output.
Active
*
Passive
*
Active
Assign current output 1 to n Select process variable for
current output.
Off
*
Volume flow
Mass flow
Corrected volume
flow
Flow velocity
Conductivity
*
Corrected
conductivity
*
Temperature
*
Electronic
temperature
Reference
electrode potential
against PE
*
Coil current shot
time
*
Noise
*
Coating measured
value
*
Test point 1
Test point 2
Test point 3
Volume flow
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
4...20 mA (4...
20.5 mA)
0...20 mA (0...
20.5 mA)
Fixed current
Country-specific:
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
0/4 mA value In the Current span parameter
(→  93), one of the
following options is selected:
4...20 mA NAMUR
(3.8...20.5 mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4... 20.5 mA)
0...20 mA (0... 20.5 mA)
Enter 4 mA value. Signed floating-point
number
Country-specific:
0 l/h
0 gal/min (us)