Operation Proline Promag H 300 PROFINET
136 Endress+Hauser
11.7 Showing data logging
The Extended HistoROM application package must be enabled in the device (order
option) for the Data logging submenu to appear. This contains all the parameters for the
measured value history.
Data logging is also available via:
Plant Asset Management Tool FieldCare →  70.
Web browser
Function range
A total of 1000 measured values can be stored
4 logging channels
Adjustable logging interval for data logging
Displays the measured value trend for each logging channel in the form of a chart
0
/ ../XXXXXXXX
175.77
40.69 l/h
-100s
A0034352
x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
If the length of the logging interval or the assignment of the process variables to the
channels is changed, the content of the data logging is deleted.
Navigation
"Diagnostics" menu → Data logging
Data logging
Assign channel 1
→  137
Assign channel 2
→  137
Assign channel 3
→  137
Assign channel 4
→  138
Logging interval
→  138
Clear logging data
→  138
Data logging
→  138
Logging delay
→  138
Data logging control
→  138