Proline Promag H 300 PROFINET Installation
Endress+Hauser 21
6 Installation
6.1 Installation conditions
6.1.1 Mounting position
Mounting location
h
A0029343
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the
next pipe elbow: h ≥ 2 × DN
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h
≥ 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of
damage to the measuring tube. This measure also prevents the system losing prime.
h
2
1
A0028981
 4 Installation in a down pipe
1 Vent valve
2 Pipe siphon
h Length of down pipe
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration.
2 x DN³
5 x DN³
A0029257