Proline Promag H 300 PROFINET Commissioning
Endress+Hauser 89
10.5.4 Selecting and setting the medium
The Select medium wizard submenu contains parameters that must be configured in
order to select and set the medium.
Navigation
"Setup" menu → Select medium
‣
Medium selection
Select medium
→ 89
Pressure compensation
→ 89
Pressure value
→ 89
External pressure
→ 89
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Select medium – Select medium type. • Liquid
• Gas
Liquid
Pressure compensation – Select pressure compensation
type.
• Off
• Fixed value
• External value
Off
Pressure value The Fixed value option or the
Current input 1…n option is
selected in the Pressure
compensation parameter.
Enter process pressure to be
used for pressure correction.
Positive floating-
point number
0 bar
External pressure The Fixed value option or the
Current input 1…n option is
selected in the Pressure
compensation parameter.
Positive floating-
point number
0 bar
10.5.5 Displaying the I/O configuration
The I/O configuration submenu guides the user systematically through all the parameters
in which the configuration of the I/O modules is displayed.
Navigation
"Setup" menu → I/O configuration
‣
I/O configuration
I/O module 1 to n terminal numbers
→ 90
I/O module 1 to n information
→ 90
I/O module 1 to n type
→ 90