Multi-Function Control ETMFC610 http://www.entecene.co.kr
GLOBAL SETTING/ COMMUNICATION/ PORTS / EHTERNET/ K-Alv Function
Range
DISABLE, ENABLE
Default
ENABLE
Step
~
Select whether to use or not the Ethernet communication connecting
status check function.
GLOBAL SETTING/ COMMUNICATION/ PORTS / EHTERNET/ K-Alv Idle Time
Range
0(OFF), 1 ~ 600 sec
Default
4
Step
1sec
If Idle status is maintained during the setting time, check the
communication connecting maintainance status.
GLOBAL SETTING/ COMMUNICATION/ PORTS / EHTERNET/ K-Alv Interval
Range
0(OFF), 1 ~ 600 sec
Default
2
Step
1sec
After checking the communication connecting status, if there isn’t any
reply during the setting time, check again the status.
GLOBAL SETTING/ COMMUNICATION/ PORTS / EHTERNET/ K-Alv Retry
Range
0~255
Default
3
Step
1
Check the communication connecting maintainance status as much as
the setting number. If there isn’t a respond, take as communication fail
and close the communication connection.
>K-Alv Func: ENABLE
>K-Alv Idle T: 4.00
K-Alv Interval: 2
>K-Alv Retry: 3
[DISABLE/ENABLE]
>K-Alv Func: ENABLE
>K-Alv Idle T: 4.00
K-Alv Interval: 2
>K-Alv Retry: 3
[0(OFF),1~600:1s]
>K-Alv Func: ENABLE
>K-Alv Idle T: 4.00
>K-Alv Interval: 2
>K-Alv Retry: 3
[0(OFF),1~600:1s]
>K-Alv Func: ENABLE
>K-Alv Idle T: 4.00
K-Alv Interval: 2
>K-Alv Retry: 3
[0~255:1]