Multi-Function Control ETMFC610 http://www.entecene.co.kr
You can confirm in “MAIN MENU / STATUS / LATCH LOGIC”.
STATUS/ LATCH LOGIC
Displays latch logic’s status.
LT01 ~ LT08 : Displays the status of the latch logic 01 ~ 08.
12.8. Diagnostic
You can confirm in “MAIN MENU / STATUS / DIGNOSTIC”
STATUS/ DIGNOSTIC
Diagnostic status of ETMFC610 and System are displayed. When a
diagnostic event occurs, the related status is displayed on “ON”. After
the diagnostic event disappears, the status changes to “OFF” status.
Use [▼] [▲] button to check all items.
DIGALM : ETMFC610 on the alarm status.
DIGERR : ETMFC610 has one error or more. When this status is
“ON, it means that there are critical errors on the system.
Thus, it makes to block all protection functions.
DIGRTC : Unusual condition on Real Time Clock(RTC)
DIGCLC : Unusual condition on Close Coil
DIGSPOW : Unusual condition on System Power
ACFAIL: External AC Power Fail status
BATBAD : Battery Voltage Bad status
NOBATT : Battery Voltage Low status
CHGBAD : Charger Voltage Fail status
PWDOWN : Power Down status (AC Fail & No Battery)
>LT01 : OFF
LT03 : OFF
LT04 : OFF
LT05 : OFF
LT06 : OFF
LT07 : OFF
LT08 : OFF
>DIGALM : OFF
>DIGERR : OFF
DIGIGBT: OFF
>DIGRTC : OFF
DIGCLC : OFF
DIGOPOW: OFF
>ACFAIL : OFF
>BATBAD : OFF
NOBATT : OFF
>CHGBAD : OFF
PWDOWN : OFF