Multi-Function Control ETMFC610 http://www.entecene.co.kr
76
EN
HANCED
TEC
HNOLOGY
7.1.3. Monitoring
Place the curser on MONITERING” in GENERAL menu, press [ENT] button to move into this
menu.
7.1.3.1. Live Line
Place the curser on “LIVE LINE” in MONITORING menu, press [ENT] button to move into this
menu.
ETMFC610 has line detect element. If one phase voltage among three phase maintains over live
detect level during a constant time, live line is detected. Live line detection setting item is same as
below.
GLOBAL SETTING / GENERAL / MONITORING / LIVE LINE / Live Line Lv
Range
0.10 ~ 1.40 xVT
Default
0.30
Step
0.01 xVT
Set the live line level and this is set in multiple of previous rating.
GLOBAL SETTING / GENERAL / MONITORING / LIVE LINE / Live Line Lv
Range
0.00~600.00 sec
Default
4.00
Step
0.01 sec
Set the delay time of live detect element.
[MONITERING]
>1.LIVE LINE
2.OPERATION COUNT
3.CONTACT WEAR
4.BATT LOAD TEST
5.BATT MANAGEMENT
6.POWER QUALITY
7.TD MONITOR
8.SYSTEM POWER
[LIVE LINE]
>Live Line Lv: 0.30
Live Line Tm: 4.00
[0.10~1.40:0.01xVT]
[LIVE LINE]
>Live Line Lv: 0.30
>Live Line Tm: 4.00
[0.00~600.00:0.01s]