Multi-Function Control ETMFC610 http://www.entecene.co.kr
6.3. Using the LCD Menu
6.3.1. Initial Screen
Important information is displayed in the initial screen for user convenience in ETMFC610.
① To move to other initial screen, press [ENT] button.
② Press [FUN] button in initial screen to move to Main menu.
③ “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE / LCD DISPLAY”
Through “Init Main Screen” in the MENU, main initial screen can be selected. After initial
booting or clearing SLEEP MODE, this initial Screen can be displayed.
Table 6-2. Initial Screen (1/3)
INITIAL SCREEN
Initial Screen 1
This screen displays status information of ETMFC610
SELF CHECK: It displays self-diagnostic information of ETMFC610.
NORMAL: It displays normal status of ETMFC610
ALARM: It displays self-diagnostic alarm of ETMFC610.
ERROR: It displays self-diagnostic error of ETMFC610. In this status,
ETMFC610 is in significantly abnormal status so, ETMFC610 blocks to
Open/Close switch.
NOTE :
If “ALARM” and “ERROR” in the self-check, ETMFC610 is in abnormal
condition. Immediately stop operation and contact Manufacturer.
CONTR.TYPE: It displays the control type of ETMFC610.
FITYPE: Control type is fault indication type.
PROTYPE: Control type is protection type.
52 CONTACT: It displays the status of switch(or CB)’s main contact
CLOSE: Displays main contact is closed.
OPEN: Displays main contact is opened.
TROUBLE: It is displayed in case of Contact status is incorrect or cable
connection is not completed.
ETMFC610
SELF CHECK [ NORMAL]
CONTR.TYPE [ FITYPE]
52 CONTACT [ CLOSE]
ENTEC E&E CO., LTD.