Multi-Function Control ETMFC610 http://www.entecene.co.kr
17
EN
HANCED
HNOLOGY
2.9. Monitoring
Broken Conduct
Function..................................................................... DISABLE/ENABLE
Pickup Level (I2/I1) .................................................. 1 to 100% in steps of 1%
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Minimum Normal Current ........................................ OFF, 1 to 630A in steps of 1A
Maximum Normal Current ........................................ OFF, 10 to 630A in steps of 1A
Pickup Level Accuracy.............................................. 5%
Timing Accuracy ....................................................... at 0 time delay (50 max)
5% of trip time or ± 20
Voltage
Under Voltage 1,2
Function………………………………………..DISABLE/ENABLE
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Minimum Normal Voltage……………………..0.10 to 1.40xVT in steps of 0.01xVT
Active Voltage Type……………………………Any One(1P)/Any Two(2P)/All Three(3P)
Over Voltage 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Active Voltage Type…………………………… Any One(1P)/Any Two(2P)/All Three(3P)
Neutral Over Voltage 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Negative Sequnce Over Voltage 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Level Accuracy .......................................................... 5%
Dropout Level ........................................................... 95 to 98% of Pickup when Over Voltage
102 to 105% of Pickup when Under Voltage
Timing Accuracy ....................................................... Max. 50 at 0 trip time delay
5% of setting time or ± 20