2.2. Type Withstand Tests
Electromagnetic Compatibility Immunity
Electrostatic Discharge Immunity : IEC 61000-4-2 : 2008
Level 3 and 6 contact, 8 air
Radiated electromagnetic field immunity : IEC 61000-4-3 : 2010
10 V/m at 80~1.0 and 1.4~2.7
Electrical Fast Transient Burst Immunity : IEC 61000-4-4 : 2012
2 kV at 5 kHz (Communication Ports)
Surge Immunity : IEC 61000-4-5 : 2017
4 kV line to line
4 kV line to earth
4 kV Comm. ports
Conducted disturbance immunity : IEC 61000-4-6 : 2013
10 V at 150 kHz ~ 80 MHz
Power frequency magnetic field immunity : IEC 61000-4-8 : 2009
100 A/m (Continuous), 1 000 A/m (3s)
Voltage dips, interruption and variation immunity : IEC 61000-4-11 : 2004
Voltage disp immunity test : 0%, 40%, 70%, 80%
Voltage interruptions immunity test : 0%
Voltage variations immunity test : 70 % / 30 cycles
Test for immunity to conducted, common mode disturbances : IEC 61000-4-16 : 2015
30 V (continuous), 300 V (short duration)
Oscillatory wave immunity : IEC 61000-4-18 : 2006
Immunity test for 1 MHz burst ; Comm: 2.5 kV, Differential : 1.0 kV
Immunity test for 100 kHz burst; Comm: 2.5 kV, Differential : 1.0 kV
Emission test : CISPR 11 , Class A