Multi-Function Control ETMFC610 http://www.entecene.co.kr
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / Daily Max I
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select the [DISABLE/ENABLE] of Daily Maximum Load Current
transmission.
DISABLE : Do not process Daily Maximum Load Current Event..
ENABLE : Process Daily Maximum Load Current.
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / Flt ‘I’ Evt
Range
NO, YES, 1SHOT
Default
1SHOT
Step
~
When occurring fault, set whether or not record AI point which is
related with fault such as fault current.
NO : Do not send the all Fault Current Sequence to Event.
YES : Send all Fault Current Sequence to Event.
1SHOT : Send the first Sequence Fault Current of Fault Sequence
to Event.
NOTE :
The Fault Current occurrence time of each Sequence is when it
becomes no voltage after experience the Fault Current.
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / BI EvtBuff Size
Range
32, 64, 128, 256
Default
256
Step
~
Set the Binary Queue Size
>AEvt Method: OFF
AEvt Skip at Ft: NO
>Daily Max I:DISABLE
Flt ‘I’ Evt: 1SHOT
BI EvtBuff Size:256
[DISABLE/ENABLE]
>AEvt Method: OFF
AEvt Skip at Ft: NO
>Daily Max I:DISABLE
>Flt ‘I’ Evt: 1SHOT
BI EvtBuff Size:256
[NO/YES/1SHOT]
>AEvt Method: OFF
AEvt Skip at Ft: NO
Daily Max I:DISABLE
>Flt ‘I’ Evt: 1SHOT
>BI EvtBuff Size:256
[32/64/128/256]