Multi-Function Control ETMFC610 http://www.entecene.co.kr
SYSTEM EVENT RECORDER
Trigger Source
Protection Elements
52A Contact
Sequence status
Front panel control
AC supply
External control
Fail operation
External input status
System alarm, etc.
Trigger Time : every 5 msec
Trigger type : Pick up and Dropout
Storage Capacity : Last 5,000 Events
SET CHANGE EVENT RECORDER
Trigger Source
Global Setting Change
Group Setting Change – Group 1/2/3/4/5/6
Storage Capacity : Total 2,000 Events
LOAD & ENERGY
1) Average Load/ Minute
Trigger Source
Demand Current – A, B, C, N
Demand Voltage – A, B, C, R, S, T
Demand Real Power – A, B, C, 3ф, Positive A, Positive B, Positive C, Positive 3ф,
Negative A, Negative B, Negative C, Negative 3ф
Demand Reactive Power – A, B, C, 3ф, Positive A, Positive B, Positive C, Positive 3ф,
Negative A, Negative B, Negative C, Negative 3ф
Demand Power Factor – A, B, C, 3ф
Demand Energy - Positive Watthour(3ф), Positive Varhour(3ф), Negative Watthour(3ф),
Negative Varhour(3ф)
Trigger Time : every 5, 10, 15, 20, 30 or 60 minutes
Storage Capacity : Total 8,640 Events