Multi-Function Control ETMFC610 http://www.entecene.co.kr
82
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL / MONITORING / BATT MANAGEMENT / Discharge Time
Range
60 ~ 6000 min.
Default
1440
Step
1 min.
Sets the time when the fully charged battery (100%) is fully discharged.
GLOBAL SETTING / GENERAL / MONITORING / BATT MANAGEMENT / Alarm Level
Range
0.00 ~ 100.00 %
Default
50
Step
0.01 %
Set the battery monitoring level.
If battery capacity is less than this set value, "BATBAD (Battery Bad)"
event occurs.
GLOBAL SETTING / GENERAL / MONITORING / BATT MANAGEMENT / Alarm Level
Range
0.00 ~ 100.00 %
Default
100
Step
0.01 %
Set the battery capacity reset value.
After this setting, it can reset battery capacity using “MAIN MENU /
MAINENANCE / DATA RESET / BATT. CAPACITY or COUNT
ALL”.
When the battery is replaced, it should be reset to the capacity for the
replaced battery according to the above procedure.
NOTE :
1. Password 3 authentication is required when entering “MENU
/ MAINENANCE / DATA RESET” menu to reset the battery
capacity.
2. Current battery capacity can be checked in “MENU /
METERING / CONTROLLERL REF” menu.
[
BATT MANAGEMENT
]
>Function: DISABLE
>Charge Time: 780
>Discharge Time:1440
Alarm Level: 50.00
Capacity Rst:100.00
[60~6000:1 m]
[
BATT MANAGEMENT
]
>Function: DISABLE
>Charge Time: 780
Discharge Time:1440
>Alarm Level: 50.00
Capacity Rst:100.00
[0.00~100.00:0.01%]
[
BATT MANAGEMENT
]
>Function: DISABLE
>Charge Time: 780
Discharge Time:1440
>Alarm Level: 50.00
>Capacity Rst:100.00
[0.00~100.00:0.01%]