RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
135
ENHANCED
TECHNOLOGY
PRIMARY SETTING / PROTECTION / GROUND FAST / Low Set Definite Time
Range
OFF, 1 ~ 600sec
Default
OFF
Step
1sec
Low set definite time is used to restrict a trip time to be a definite time
adjacent to a pickup current by T-C curve. When the trip time is greater
than the low set definite time, low set definite time is applied for
operation.
NOTE :
This setting is supported from version 6.03 of EVRC2A-N6,
NT.
Ground Delay Time Overcurrent Setup
The ground delay time overcurrent settings process is very similarly to the ground fast time
overcurrent.
[GROUND FAST]
>M.R.T: 0.00
>Reset Method: INST
>Low Set DT: OFF