EasyManua.ls Logo

Entec EVRC2A-N6-NT - 2.6. Recorder

Default Icon
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
19
ENHANCED
TECHNOLOGY
2.6. Recorder
WAVEFORM CAPTURE
y Trigger Source
Protection pickup Elements
Trip command active
y Data Channels
5 currents, 4 voltages, 85 logic input states, 8ch output relays, 8ch Input
y Sample Rate : 16 per cycle
y Trigger Position : 1 to 15cycle
y Storage capacity : 32 events with 15cycle
SYSTEM EVENT RECORDER
y Trigger Source
Protection Elements
52A Contact
Sequence status
Front panel control
AC supply
External control
Fail operation
External input status
System alarm
V1(Source), V2(Load)
Power Quality detect, etc.
y Trigger Time : each 1/4 cycle
y Trigger type : Pick up and Dropout
y Storage Capacity : Last 2048 Events

Table of Contents