7) Stored value Clear
Select “8. WEAR MONITOR” in “PRIMARY SETTING / RELAY SETUP / CLEAR
SAVED DATA” to clear value. Insert the value set in “PRIMARY SETTING /
MONITORING / RECLOSER WEAR / A, B, C Wear” from LCD menu.
8.5. Battery Test
PRIMARY SETTING / MONITORING / BATTERY TEST / BT Time(day)
Range
0(OFF), 1 ~ 7 day
Default
OFF
Step
1 day
Select the period for automatically checking the battery status.
[BATTERY TEST]
>BT Time(day): OFF