RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
80
ENHANCED
TECHNOLOGY
5.7. Gas Sensor Type
Move to “PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP / GAS
SENSOR TYPE” to select setting for the gas sensor type.
PRIMARY SETTING / RELAY SETUP / GAS SENSOR TYPE
Range
NONE, TYPE1, TYPE2
Default
NONE
Step
~
NONE : Gas Sensor is not used.
TYPE1 : Set TYPE1 if Recloser manufactured before JUNE, 2005.
TYPE2 : Set TYPE2 if Recloser manufactured from JULY, 2005.
NOTE :
According to a recloser type, they may be no this setting on the menu.
5.8. Time Set & Display Type – Option
It is to set Date Display for all related Menu.
Move to “PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP / TIME
SET&DIS TYPE”.
RELAY SETUP / TIME SET&DIS TYPE / GMT Sign*
Range
+,-
Default
+
Step
~
Set GMT time and the local time off-set direction. Local time is faster
than GMT time, select ‘+’, otherwise, select ‘-’.
RELAY SETUP / TIME SET&DIS TYPE / GMT Hour*
Range
0~23
Default
0
Step
1
Set the hour difference between local time and GMT.
[TIME SET&DIS’TYPE]
>Set Type: LOCAL
>GMT Sign: -
>GMT Hour: 0
[TIME SET&DIS’TYPE]
>Set Type: LOCAL
>GMT Sign: -
>GMT Hour: 0
[GAS SENSOR TYPE]
>Type Select: TYPE2