RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
8
ENHANCED
TECHNOLOGY
2.2. Type Withstand Tests
Dielectric Strength
y CT inputs, VT inputs, Control Power inputs, Opto-isolated inputs and Relay outputs
2(60) for 1 minute
Impulse Voltage
y IEEE C62.45 (1992) Withstand Capability of Relay Systems to Radiated Electromagnetic
Interference Transceivers, 6(1.2×50), 3(8×20)
Surge Withstand Capability
y IEEE C37.90.1 - 1989 IEEE SWC Tests for Protective Relays and Relay Systems
(3 oscillatory 1 to 1.5, 5 fast transient 1.2×50)
y IEEE C37.90.2 - 1987 IEEE Trial-Use Standard, Withstand Capability of Relay Systems to
Radiated Electromagnetic Interference from Transceivers, 10 V/m
(150 and 450, 5 W transmitter 10)
Vibration Test
y IEC 255-21-1 - 1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2.
Control Operating Temperature
y Operating range : -25℃∼+70(-13℉∼+158)
y LCD : -20℃∼+70(-4℉∼+158) - standard
y VFD : -40℃∼+85(-40℉∼+185) - option(Vacuum Fluorescent Display)