Phase/Ground/Negative Sequence Time Overcurrent Protection
Pickup Level .............................................................. OFF, 10 to 1600 in steps of 1A
Dropout Level ........................................................... 96 to 98% of Pickup
Curve Type
ANSI : Moderately, Normally, Very, Extremely, Short Inverse, Definite Time (1s ,10s)
IEC : Standard, Very, Extremely, Long, Short Inverse
ESB : Normally, Very, Long Very Inverse
User programmable curves : U1, U2, U3, U4
McGraw-Edison : Non Standard Curves 37
Time dial ................................................................... 0.05 to 15.00 in steps of 0.01
Time adder ................................................................. 0.00 to 10.00 in steps of 0.01s
Minimum Response time .......................................... 0.00 to 10.00 in steps of 0.01s
Reset Type ................................................................. Instantaneous/Linear
Low Set Definite Time .............................................. 1 ~ 600 in steps of 1s
(supported from Ver 6.03 of EVRC2A-N6,NT)
Pickup Level Accuracy.............................................. 5%
Timing Accuracy ....................................................... ± 5% of trip time or ± 20
Phase/Ground/Negative Sequence Instantaneous Overcurrent Protection
Pickup Level .............................................................. OFF, 10 to 20000 in steps of 1A
Dropout Level ........................................................... 95 to 98% of Pickup
Time Delay ................................................................ 0.00 to 10.00 in steps of 0.01s
Active Trip ................................................................ 1 to 5 in steps of 1
Pickup Level Accuracy.............................................. 5%
Timing Accuracy ....................................................... at 0 time delay (50 max)
5% of trip time or ± 20
Phase/Ground/Negative Sequence High Current Lockout Protection
Pickup Level .............................................................. OFF, 10 to 20000 in steps of 1A
Dropout Level ........................................................... 95 to 98% of Pickup
Time Delay ................................................................ 0.00 to 10.00 in steps of 0.01s
Active Trip ................................................................ 1 to 5 in steps of 1
Pickup Level Accuracy.............................................. 5%
Timing Accuracy ....................................................... at 0 time delay (50 max)
5% of trip time or ± 20

Table of Contents