RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
12
ENHANCED
TECHNOLOGY
Sensitive Earth Definite Time Overcurrent Protection
Pickup Level
*NOTE
..................................................... OFF, 4 to 160 in steps of 1A(prior to Ver 6.15)
OFF, 1 to 160 in steps of 1A(from Ver 6.15)
Dropout Level ........................................................... 95 to 98% of Pickup
Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s
Pickup Level Accuracy .............................................. 5%
Timing Accuracy ....................................................... at 0 time delay (50 max)
5% of trip time or ± 20
NOTE
As per the users request, for the products that are dispatched with ZCT installed, the “Pickup
Level” setting range of the protection element is “OFF, 0.1 to 16.0 in steps of 0.1A”. To check
whether the product is dispatched with ZCT installed, check
“MAIN MENU/ STATUS/
CONTROL TYPE”
menu.
Reclose Control
Operations to Lockout - phase trip ............................ 1 to 5 in steps of 1
Operations to Lockout - ground trip .......................... 1 to 5 in steps of 1
Operations to Lockout - SEF trip .............................. 1 to 5 in steps of 1
Operations to Lockout - Negative Seq’ trip ............... 1 to 5 in steps of 1
Operations of Fast curve - phase trip ......................... 0 to 5 in steps of 1
Operations of Fast curve - ground trip ...................... 0 to 5 in steps of 1
Operations of Fast curve - Negative Seq’ trip ........... 0 to 5 in steps of 1
Reclose interval 1 ...................................................... 0.50 to 600.00 in steps of 0.01(prior to Ver 6.11)
0.10 to 600.00 in steps of 0.01(from Ver 6.11)
Reclose interval 2 ...................................................... 1.00 to 600.00 in steps of 0.01
Reclose interval 3 ...................................................... 1.00 to 600.00 in steps of 0.01
Reclose interval 4 ...................................................... 1.00 to 600.00 in steps of 0.01
Reset time for Auto Reclose Cycle ............................ 1.00 to 600.00 in steps of 0.01
Reset time from lockout ............................................ 1.00 to 600.00 in steps of 0.01
Timing Accuracy ....................................................... ± 5%