RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5
ENHANCED
TECHNOLOGY
2. TECHNICAL SPECIFICATIONS
2.1. Inputs and Outputs
Systems
y 3phase-3wire or 3phase-4wire, 38 maximum, 800 Amp maximum
Frequency
y 50 / 60 system and ABC/ACB phase rotation
Control Voltage Input
y AC Voltage Input 110V/220Vac or other voltage (+10%,-15%)
y Nominal Battery Voltage : 24Vdc
y Based on user requirement, prepare 110V/220V Selectable Switch - Option
User available DC power Output - Option
y DC Power Voltage : 12, 15, 24Vdc
y DC Power Continuous : 40W
y DC Power for 60Sec : 60W
Voltage Divider Inputs (VD) - Standard
Capacitor Voltage Divider Inputs (CVD) – Only EVR
y Maximum Input Voltage : 5V
y Burden : 2e-6 VA
y System Voltage : 15, 27, 38
y Capacitor value
- Phase Capacitor value : 20
Resistance Voltage Divider Inputs (RVD) – Only EPR
y Maximum Input Voltage : 5V
y Burden : Bow 0.0015 VA
y System Voltage : 15, 27
y Resistance value
- Phase Resistance value : 100M

Table of Contents