EasyManua.ls Logo

Entec EVRC2A-N6-NT - Page 91

Default Icon
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
81
ENHANCED
TECHNOLOGY
RELAY SETUP / TIME SET&DIS TYPE / GMT Min*
Range
0~59
Default
0
Step
1
Set the minute difference between local time and GMT.
NOTE
Korea Local time is 9 hour faster than UTC time, set it as follows (+9:00);
Sing : +, Hour : 9, Min : 0
NOTE
If the setting values associated with GMT are set up incorrectly, the problems can be happened
as follows.
- If the "Time Syn’ Ref" is set to be GMT, the time of the internal clock in EVRC2A can
be changed incorrectly at time synchronization.
- If the time type of the DNP communication event is set to be GMT, the time of event
transmitted is not correct.
NOTE :
The above set values marked with * are indicated from Ver 6.15 of EVRCA.
RELAY SETUP / TIME SET&DIS TYPE / Disp’ Type
Range
YMD, MDY
Default
YMD
Step
~
YMD : it displays in turn Year / Month / Date
MDY : it displays in turn Month / Date / Year
RELAY SETUP / TIME SET&DIS TYPE / Time Syn’ Ref
Range
LOCAL, GMT
Default
GMT
Step
~
Set Reference Time Type when time need in a device is synchronized
with GPS(or IRIG).
NOTE :
The setting is supported from Ver 7.04 of EVRC2A_NT.
[TIME SET&DIS’TYPE]
>GMT Min : 0
>Disp’ Type: YMD
>Time Syn’ Ref: GMT
[TIME SET&DIS’TYPE]
>GMT Min : 0
>Disp’ Type: YMD
>Time Syn’ Ref: GMT
[TIME SET&DIS’TYPE]
>GMT Hour: 0
>GMT Min : 0
>Disp’ Type: YMD

Table of Contents