RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
173
ENHANCED
TECHNOLOGY
PRIMARY SETTING / PROTECTION / VOLTAGE / OVER VOLTAGE 1 / Time Delay
Range
0.00 ~ 600.00 sec
Default
5.00
Step
0.01 sec
Set the definite time delay.
PRIMARY SETTING / PROTECTION / VOLTAGE / OVER VOLTAGE 1 / Pickup Type
Range
1P, 2P, 3P
Default
1P
Step
~
Select the type of phase required for operation.
1P : Function operates when one or more than one phase voltage value
is over the pickup voltage level.
2P : Function operates when two or more than two phase voltage
values are over the pickup voltage level.
3P : Function operates when all three phase voltage values are over the
pickup voltage level.
Overvoltage 2 Setup
The overvoltage 2 settings process a very similar method to the overvoltage 1.
[OVER VOLTAGE 1]
Pickup(xVT): 1.20
Time Delay : 5.00
>Pickup Type: 1P
[OVER VOLTAGE 1]
Relays(0-8): OFF
Pickup(xVT): 1.20
>Time Delay : 5.00