RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
176
ENHANCED
TECHNOLOGY
PRIMARY SETTING / PROTECTION / FREQUENCY / Min. V(xVT)
Range
0.00 ~ 1.25
Default
0.10
Step
0.01
Enter the minimum voltage required to allow the frequency element to
Operate.
PRIMARY SETTING / PROTECTION / FREQUENCY / Min. I(A)
Range
10 ~ 1600A
Default
10
Step
1A
Enter the minimum value of current required for any phase to allow the
frequency element to operate.
PRIMARY SETTING / PROTECTION / FREQUENCY / NFCL Func’
Range
OFF, ON
Default
OFF
Step
~
Enable or disable “CLOSE” function when the frequency becomes
normal.
PRIMARY SETTING / PROTECTION / FREQUENCY / NFCL TD
Range
0.0 ~ 6000.0 sec
Default
60.0
Step
0.1
Set the time delay before “CLOSE” operation.
[FREQUENCY]
>Min. I(A): 0.01
>NFCL Func’: OFF
>NFCL TD: 60.0
[FREQUENCY]
>Min. I(A): 10
>NFCL Func’: OFF
>NFCL TD: 60.0
[FREQUENCY]
>Over TD: 6.00
>Min. V(xVT): 0.10
>Min. I(A): 10
[FREQUENCY]
>Over TD: 6.00
>Min. V(xVT): 0.10
>Min. I(A): 10