RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
179
ENHANCED
TECHNOLOGY
PRIMARY SETTING / PROTECTION / OTHER ELEMENT / F/I Reset
Range
AUTO, MANUAL
Default
AUTO
Step
~
Faulted Indicator reset method
AUTO : Reset shall be performed by pressing [FI RESET] button or
shall be performed automatically after High Voltage line becomes
normal.
MANUAL : It shall be reset by pressing [FI RESET] button.
PRIMARY SETTING / PROTECTION / OTHER ELEMENT / D/T M-Close
Range
0.00 ~ 600.00 sec
Default
0.00
Step
0.01 sec
Time delay for manual close
[OTHER ELEMENT]
L.O Priority: GND
F/I Reset: AUTO
>D/T M-Close: 0.00
[OTHER ELEMENT]
Seq’ Coordi’: OFF
L.O Priority: GND
>F/I Reset: AUTO