RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
248
ENHANCED
TECHNOLOGY
12.3.4. Related Setting Menu
1) ON/OFF Setting
Load Profile can be set ON/OFF by user.
PRIMARY SETTING / RELAY SETUP / EVENT RECORDER / Load Profile
Range
OFF, ON
Default
ON
Step
~
ON : Records load profile.
OFF : No record of load profile.
2) Recording time interval setting
PRIMARY SETTING / RELAY SETUP / EVENT RECORDER / L.P save time(m)
Range
5, 10, 15, 20, 30, 60 min
Default
15
Step
~
Sets the interval time between Records.
12.3.5. Stored value Clear
Select “3. LOAD PROFILE” in “PRIMARY SETTING / RELAY SETUP / CLEAR SAVED
DATA” to clear.
[EVENT RECORDER]
Len' of Pre F: 4
Load Profile: ON
>L.P save time(m):15
[EVENT RECORDER]
Fault Cycle: ON
Len' of Pre F: 4
>Load Profile: ON