RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
21
ENHANCED
TECHNOLOGY
POWER QUALITY EVENT RECORDER - Option
y Trigger Source
 Trigger elements : Source, Load
y Trigger Time : each 1/4 cycle
y Trigger type : supply outage occurrence, sag occurrence, swell occurrence, voltage unbalance
occurrence, current unbalance occurrence
NOTE :
The detection of voltage/current unbalance is supported from version 6.12 of
EVRC2A-N6,NT.
y Storage Capacity : Last 512 Events
COUNTER
y Trip Counter : 0 to 65,534
y Fault Counter : 0 to 65,534
y System Restart Counter : 0 to 65,534
y Supply Outage Counter : 0 to 60,000 - Option
y Supply Outage Time : 0 to 9,999 hours - Option
y Sag Counter : 0 to 60,000 - Option
y Swell Counter : 0 to 60,000 – Option
y Voltage Unbalance(Source Side) Counter : 0 to 60,000 - Option
y Voltage Unbalance(Load Side) Counter : 0 to 60,000 - Option
y Current Unbalance Counter : 0 to 60,000 - Option
RECLOSER WEAR
y Phase A Wear : 0.0 to 100.0%
y Phase B Wear : 0.0 to 100.0%
y Phase C Wear : 0.0 to 100.0%