EasyManua.ls Logo

ero electronic MKC - Out 1 and 2 - SSR; Servomotor Output; Analog Outputs

Default Icon
141 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
110
STANDARD RANGES TABLE
C) LINEAR INPUTS
Read-out: keyboard programmable between -1999 and +9999.
Decimal point: programmable in any position
STANDARD RANGES TABLE
NOTE: for TC type B the accuracy is guaranteed for tempera-
ture higher than 500 °C (950 °F).
B) RTD (Resistance Temperature Detector)
Input: for RTD Pt 100 W, 3-wire connection;
°C/°F selectable.
Measuring current: 140 mA typical.
Line resistance: automatic compensation up to 20 W/wire with no
measurable error.
- 200 / + 850 °C
- 330 / + 1560 °F
Input type
RTD Pt 100 W
IEC 751
Ranges
15
30
Input type
37
38
31
32
33
34
35
36
0 - 60 mV
12 - 60 mV
0 - 20 mA
4 - 20 mA
0 - 5 V
1 - 5 V
0 - 10 V
2 - 10 V
impedance
> 1 MW
< 5 W
> 200 kW
> 400 kW
T/C
type
N
S
R
B
G
D
C
Ni
Ranges
22
23
24
25
26
27
28
29
-150 / 2550 °F
- 60 / 3200 °F
- 60 / 3200 °F
32 / 3300 °F
0 / 4170 °F
0 / 4170 °F
0 / 4170 °F
0 / 2190 °F
IEC 584-1
IEC 584-1
IEC 584-1
IEC 584-1
Xkc-1-C0.P65 5/29/02, 11:59 AM110

Table of Contents