CnF. 2
43
1) its value is < 0 and only one control output is configured;
2) servomotor open loop without feedback is configured.
B) The parameter “SF.Cn” ("Condition for output safety value"
[C.G07]) will be forced to "standard" (“Std.”) if it is not
complied with configured control output type
C) The parameter “SF.UL” ("Output safety value" [C.G08]) will
be forced to 0 if only one control output is configured and its
value is < 0.
D) The parameter “Fd.Fn” ("Out failure detection current
measurement" [C.I11]) will be forced to “nonE” if it is
assigned to a control output different from a time
proportional output.
E) The parameter “Fd.Ou” ("Out failure detection output
assignment" [C.I13]) will be forced to “nonE” if it is
assigned to an output configured as control output
F) The parameter “IP” ("Integral pre-load" [r.d05]) will be forced
to 50.0 if only one control output is configured and its value is
< 0
CONFIGURATION GROUP 3 [C.Fxx]
CONTROL OUTPUT CONFIGURATION
- Split range - [C.F01]
This parameter will be available only when two control outputs
are configured.
Range: dIS = Split range feature is not required
Enb = Split range feature is required
NOTE about the split range.
This function allows you to drive by the same control action, two
physical outputs (two actuators) with different bias and gain.
The relation between the Calculated Power Output and the
resulting real outputs are shown below:
CnF. 3
Xkc-1-C0.P65 5/29/02, 11:59 AM43