Anti reset windup: from 10 % to 200 % of the input span.
Main output cycle time: from 1 second to 200 seconds.
Secondary output cycle time: from 1 second to 200 seconds.
Relative secondary output gain: keyboard programmable from
0.20 to 2.00 referred to the proportional band.
Overlap / dead band : keyboard programmable from - 20 %
(dead band) to + 50 % (overlap) of the proportional band.
Output limiters.
For the main and/or secondary control outputs it is possible to
set:
- output high limits
- output low limits
- output max. rate of rise.
AUTO/MANUAL mode: selectable by front push-button or logic
input.
OUTPUTS
Control output updating time :
- 125 ms when a linear input is selected
- 250 ms when a TC or RTD input is selected.
Action: direct/reverse programmable
Output level limiter:
- high and low limits for main control output
- high and low limits for secondary control output.
Out 1 and 2
Function: singularly programmable as
- Control output
- Alarm output
- Event output.
Type: Relay, SSR or TRIAC.
Out 1 and 2 - Relay
Relay type: SPDT
Contact rating: 3 A @ 250 V on resistive load.
Xkc-1-C0.P65 5/29/02, 11:59 AM113