73
LAMP TEST
When it is desired to verify the display efficiency, put the
instrument in "normal display mode" and push t and MENU
push-buttons for more than 5 s.
The instrument will turn ON, with a 50 % duty cycle, all the LEDs
of the display (we define this function "LAMP TEST").
No time out is applied to the LAMP TEST.
When it is desired to come back to the normal display mode,
push any push-button.
During the LAMP TEST the instrument continues to control the
process.
SMART FUNCTION
It is used to automatically optimize the control action.
To enable the SMART function proceed as follows:
1) push the MENU push-button until "Gr. 2" run time parameter
group is shown.
2) push the FUNC push-button until "Sñrt" parameter is shown.
3) push s or t and set the "On" indication on the middle
display;
4) push the FUNC push-button.
The ST LED will turn on or flashing according to the selected
algorithm.
When the smart function is enabled, it is possible to display but not
to modify the control parameters.
To disable the SMART function proceed as follows:
1) push the MENU push-button until "Gr. 2" run time parameter
group is shown.
2) push the FUNC push-button until "Sñrt" parameter is shown.
3) push s or t and set the "OFF" indication on the middle
display;
4) push the FUNC push-button.
The ST LED will turn off.
The instrument maintains the current set of control parameters
and it enables parameter modification.
NOTES : 1) When ON/OFF control is programmed (Pb=0), the
SMART function is disabled.
2) The SMART enabling/disabling can be protected
by safety key.