84
Gr.5
NOTES:
1) When device is configured with two control outputs (split
range excluded) the control action is forced to reverse and it
cannot be modify.
2) When direct/reverse selection is performed by a logic input
this parameter allows you to monitor the current selected
action only.
- Group 4 default data loading - [r.d09]
Range: OFF = No loading data
ON = Loading data
Run time group 5 [r.Exx]
AUXILIARY CONTROL PARAMETER
- Anti reset wind up - [r.E01]
This parameter is available when at least one control output is
configured and "Pb" [r.d01] is different from 0.
Range: from 10% to 200% of the input span
- Servo motor travel time - [r.E02]
This parameter is available when the open loop servomotor
control drive output is configured (“O3.Fn” [C.E03] is equal to
“ñC.Sñ” or “SC.Sñ” and “Sñ.tP” [C.E05] are equal to “OPEn”).
Range: from 0.12 to 3.00 m.ss
REVERSE ACTION DIRECT ACTION
t
Input
t
Output
t
Input
t
Output