Gr.5
87
- Set point high limit - [r.E13]
Range: from rL [r.E12] to “ñ.In.H” [C.d06].
NOTES: Whenever “ñ.In.H” [C.d06] has been modified, the
following occurs:
1) rH will be realigned to it;
2) if the set point values are out of the new limits, "rH"
automatically assumes the default value.
- Rate of change for positive set point
variations - [r.E14]
Range: from 1 to 200 digits per minute.
Above this value the display shows “Inf” and the transfer will be
a step change.
- Rate of change for negative set point
variations - [r.E15]
Range: from 1 to 200 digits per minutes.
Above this value the display shows “Inf” and the transfer will be
a step change.
- Time out for the soft start - [r.E16]
This parameter is available when at least one output is
configured as control output and no logic input is configured as
“Output limiter activator”.
Range: from 1 to 540 min.
Above this value the display shows “InF” and the limiting action
is always active.
NOTE: The tOL can be always modified but the new value will be
used only at the next device power up
Xkc-1-C0.P65 5/29/02, 11:59 AM87