- Secondary control output low limit - [r.E08]
This parameter is available when one control output is
configured as secondary control output.
Range: From 0.0 % of the output span to S.OLH [r.E09].
- Secondary control output high limit - [r.E09]
This parameter is available when one control output is
configured as secondary control output.
Range: from S.OLL [r.E08] to 100.0 % of the output span
- Secondary control output max rate of rise
- [r.E10]
This parameter is available when one control output is
configured as secondary control output.
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES:
1) This parameter will be active even if device is configured for
On/OFF control.
2) During the transfer from AUTO to MANUAL, if this action is
programmed as a not bumpless transfer, the “S.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.
- Secondary output cycle time - [r.E11]
This parameter is available when a time proportional secondary
control output is configured.
Range: from 1 to 200 s
- Set point low limit - [r.E12]
Range: From “ñ.In.L” [C.d05] to rH [r.E13].
NOTES: Whenever “ñ.In.L” [C.d05] has been modified, the
following occurs:
1) rL will be realigned to it;
2) if the set point values are out of the new limits, the set point
automatically assumes the default value.