CnF. 3
46
This instrument allows you to select an output linearization in
accordance with the two most common valve flow characteris-
tics:
- Quick opening
- Equal percentage.
- Main control output in engineering unit
- [C.F07]
This parameter will be available only when main control output is
configured.
Range: nO = Scalable is not required
YES = Scalable is required
NOTE: This scaling allows you to display the output value in
engineering units instead of in percent.
- Main output decimal point position - [C.F08]
This parameter will be available only when "ñ.SCL" ("Main
control output in engineering units" [C.F07]) is set to "yES".
Range:
----. = No decimal figure
---.- = One decimal figure.
--.-- = Two decimal figures.