SECTION 1 – EQUIPMENT
UL / ULC Ex4623 Fike Clean Agent System w/ FM-200™ Page 25 of 25
FM 3010715 Manual P/N: 06-215 (Rev G) Revision Date: January, 2010
1.13 CONTROL SYSTEM & ACCESSORIES
Fike offers several options to allow the user to interface with the Detection & Control system as needed to suit
their specific needs. The following control systems and accessories are considered to be specific to Clean Agent
systems, and will be required in various configurations. This is not intended to be a complete reference for the
Detection & Control System that will be required. The devices not shown here include detectors (heat & smoke),
audio/visual devices, I/O devices, power supplies, etc. Refer to the appropriate Detection & Control Manual for
the system and/or device in question for additional information.
1.13.1 CONTROL PANELS
The control panel utilized with a Fike Fire Suppression System
MUST be a UL Listed releasing device for GCA and/or initiator-
operated discharge valves. Fike offers several control panel
options, each having both automatic and manual actuation
capabilities, and each supplied with battery back-up capabilities.
The following Fike Detection & Control Panels are UL Listed and
FM approved for use with Fike Clean Agent Systems:
• SHP Pro
• Cheetah Xi
• Cheetah Xi50
1.13.2 MANUAL ACTUATOR
The Fike Manually Operated Actuator (P/N 10-2225) provides an
independent means of operating a Fike Clean Agent System that utilizes
GCA’s. The unit consists of a manually-operated DC generator and a
supervisory module. This device will activate the Clean Agent system
without the need for external power or stored energy, thereby providing a
fail-safe method of activation. To operate the Manual Actuator, simply pull
the break-seal and push the handle up a quarter turn. This action
generates the power necessary to activate the GCA..
The Manual Actuator can be used as a stand-alone device, or in
conjunction with a detection & control system as a back-up operator. Each
unit is capable of activating up to six GCA’s each, and the wiring is
supervised when the unit is hooked-up to a suitable control panel.
The Manual Actuator is housed in an 11” x 7” x 6” (279 mm x 178 mm x
152 mm) enclosure that should be mounted as close to the containers as
possible.
Refer to Fike Manual 06-152 for additional design, installation, and maintenance information for this device.
Note: This device is not FM approved.