SECTION 2 – DESIGN
UL / ULC Ex4623 Fike Clean Agent System w/ FM-200™ Page 25 of 39
FM 3010715 Manual P/N: 06-215 (Rev G) Revision Date: January. 2010
2.9.3 LIQUID ARRIVAL TIME
The amount of time necessary for the liquid HFC-227ea to arrive at each nozzle must be within one (1) second of
each other. For example, if the liquid agent takes two (2) seconds to arrive at the first nozzle, (the closest nozzle
to the container), the liquid arrival time to all of the remaining nozzles cannot exceed three (3) seconds.
2.9.4 LIQUID RUNOUT TIME
The amount of time necessary for the liquid HFC-227ea to discharge (runout) of each nozzle must be within 2.1
seconds of each other. For example, if the liquid runout time for the first nozzle takes 3 seconds, the runout time
for all of the remaining nozzles must not exceed 5.1 seconds.
2 SEC.
2.5 SEC.
3 SEC.
3 SEC.
4.9 SEC.
4.9 SEC.
5.1 SEC.