SECTION 2 – DESIGN
UL / ULC Ex4623 Fike Clean Agent System w/ FM-200™ Page 5 of 39
FM 3010715 Manual P/N: 06-215 (Rev G) Revision Date: January. 2010
Temp.
Specific
Vapor
Volume
Weight Requirements of Hazard Volume, W/V (kg/m
3
)
b
(Metric Units)
t s HFC-227ea Design Concentration (% by Volume)
e
(
o
C)
c
(m
3
/kg)
d
6 6.25 6.5 6.8 7 8 9 10 11 12
-10 0.1215 0.5254
0.5487 0.5722 0.6005
0.6196 0.7158 0.8142 0.9147 1.0174 1.1225
-5 0.1241 0.5142
0.5372 0.5602 0.5879
0.6064 0.7005 0.7967 0.8951 0.9957 1.0985
0 0.1268 0.5034
0.5258 0.5483 0.5754
0.5936 0.6858 0.7800 0.8763 0.9748 1.0755
5 0.1294 0.4932
0.5152 0.5372 0.5638
0.5816 0.6719 0.7642 0.8586 0.9550 1.0537
10 0.1320 0.4834
0.5051 0.5267 0.5527
0.5700 0.6585 0.7490 0.8414 0.9360 1.0327
15 0.1347 0.4740
0.4949 0.5161 0.5417
0.5589 0.6457 0.7344 0.8251 0.9178 1.0126
20 0.1373 0.4650
0.4856 0.5063 0.5314
0.5483 0.6335 0.7205 0.8094 0.9004 0.9934
25 0.1399 0.4564
0.4765 0.4969 0.5215
0.5382 0.6217 0.7071 0.7944 0.8837 0.9750
30 0.1425 0.4481
0.4678 0.4879 0.5120
0.5284 0.6104 0.6943 0.7800 0.8676 0.9573
35 0.1450 0.4401
0.4598 0.4794 0.5032
0.5190 0.5996 0.6819 0.7661 0.8522 0.9402
40 0.1476 0.4324
0.4517 0.4710 0.4943
0.5099 0.5891 0.6701 0.7528 0.8374 0.9240
45 0.1502 0.4250
0.4439 0.4628 0.4858
0.5012 0.5790 0.6586 0.7399 0.8230 0.9080
50 0.1527 0.4180
0.4366 0.4553 0.4778
0.4929 0.5694 0.6476 0.7276 0.8093 0.8929
55 0.1553 0.4111
0.4293 0.4476 0.4698
0.4847 0.5600 0.6369 0.7156 0.7960 0.8782
60 0.1578 0.4045
0.4225 0.4405 0.4624
0.4770 0.5510 0.6267 0.7041 0.7832 0.8641
65 0.1604 0.3980
0.4156 0.4334 0.4549
0.4694 0.5423 0.6167 0.6929 0.7707 0.8504
70 0.1629 0.3919
0.4092 0.4268 0.4479
0.4621 0.5338 0.6072 0.6821 0.7588 0.8371
75 0.1654 0.3859
0.4031 0.4203 0.4411
0.4550 0.5257 0.5979 0.6717 0.7471 0.8243
80 0.1679 0.3801
0.3971 0.4140 0.4346
0.4482 0.5178 0.0589 0.6617 0.7360 0.8120
85 0.1704 0.3745
0.3912 0.4080 0.4282
0.4416 0.5102 0.5803 0.6519 0.7251 0.8000
90 0.1730 0.3690
0.3854 0.4018 0.4217
0.4351 0.5027 0.5717 0.6423 0.7145 0.7883
a
The manufacturer’s listing specifies the temperature range for operation.
b
W/V [agent weight requirements (kg/m
3
)] = pounds of agent required per m
3
of protected volume needed
to produce the indicated concentration at the temperature specified.
c
t [temperature (
o
C)] = the design temperature in the hazard area.
d
s [specific volume (m
3
/kg)] = specific volume of superheated HFC-227ea vapor can be approximated by
the formula: s = 0.1269 + 0.0005(t)
e
C [concentration (%)] = volumetric concentration of HFC-227ea in air at the temperature indicated.