SECTION 3 – SAMPLE PROBLEM
Page 4 of 17 Fike Clean Agent System w/ FM-200™ UL / ULC Ex4623
Revision Date: January, 2010 Manual P/N: 06-215 (Rev G) FM 3010715
Step 3: Locate the nozzle(s) on a scaled plan view of the hazard areas being protected. This will allow you to
check the area coverage of each nozzle being used. This will also determine if you use 180
o
or 360
o
nozzles, or
a combination of the two.
COMPUTER ROOM
UPS ROOM
OPERATIONS RM
5'
[1.52m]
10'
[3.05m]
9'-6"
[2.90m]
29'
[8.84m]
15'
[4.57m]
33'
[10.06m]
48'
[14.63m]
25'-6"
[7.77m]
12'
[3.66m]
14'-6"
[4.42m]
FIGURE 3.3.2-A
48'
[14.63m]
29'
[8.84m]
COMMON SUBFLOOR
24'
[7.32m]
14'-6"
[4.42m]
FIGURE 3.3.2-B