6-24
MHT260a (Engl.)
(8) Basic parameter 51
Para. Name Setting range Initial value Change
51 Speed matching zone (width) 10 to Max. speed [r/min] (in 1 step) 50 Always
The speed arrive signal is turned on when the motor speed is near the reference speed (set by para.) As the initial value is 50 [r/min], the
speed arrive signal is on when the motor speed reaches the reference speed ±50 [r/min].
When the motor speed does not reach the reference speed due to the max. speed setting (basic. para. 16) or override setting, this signal
turns off. When [FWD] or [REV] signal is off, the speed arrive signal does not turn on.
(9) Basic parameter 52
Para. Name Setting range Initial value Change
52 Speed zero width 10 to max. speed [r/min] (in 1 step) 20 Always
The output range of the speed zero [NZERO] signal can be set. The minimum unit is 1 [r/min].
(10) Basic parameter 53
Para. Name Setting range Initial value Change
53 Deviation zero width 10 to 10000 [pulse] (in 1 step) 200 Always
The range while the deviation zero signal is on can be set. The setting value is the encoder pulse count.
Speed
Time
Speed matching zone (width)
basic para. 51
Forward command [FWD]
Speed arrive [NARV]
OFF
OFF
ON
OFF
ON
ON