6-27
MHT260a (Engl.)
(16) Basic parameter 66
Para. Name Setting range Initial value Change
66 Origin detection range 0, 1 to 10000 [pulse] (in 1 step) 0 Always
The origin return end signal ON width can be set.
The signal is on within the range of the basic para. 66 setting, based on the position at origin return end or at the position preset signal
position.
(17) Basic parameter 72 to 78
Para. Name Setting range Initial value Change
72 Origin return direction 0: Positive direction 1: Negative direction 0 Power
73 Z-phase detection valid/invalid 0: Valid 1: Invalid 0 Power
74 Origin LS logic 0: NO contact 1: NC contact 0 Always
75 Origin return speed 0.01 to max. speed [r/min] (in 0.01 step) 500.00 Always
76 Origin detection creep speed 0.01 to max. speed [r/min] (in 0.01 step) 50.00 Always
77 Origin shift 1 to 2000000 [pulse] (in 1 step) 50000 Always
78 2nd origin 2 to max. division number (in 1 step) 2 Power
These parameters are related to the origin return action.
For details, see 5.4.1 Origin return.
(18) Basic parameter 81
Para. Name Setting range Initial value Change
81 Manual indexing 0: Shortest 1: Invalid 2: Station number 0 Power
During manual operation, the stopping position when the signal [FWD/REV] is off can be set.
For details, see 5.3.1 Forward command/Reverse command.